12M9-008-B2

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.00 (1)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.00 (1)
  • Click a star to rate this product
GE Multilin MM300 IO_C Module

AVAILABILITY:

IN STOCK
SHIPS IN 3-5 DAYS

Sell Surplus: Have a 12M9-008-B2 to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: 12M9-008-B2
  • SKU: 12M9008B2GM
  • Manufacturer: GE Multilin
  • Series: MM300 Motor Manager

12M9-008-B2 Technical Specifications

Manufacturer General Electric Multilin (GE)
Manufacturing Location Markham, Ontario, Canada
Software EnerVista
Model Number 12M9-008-B2

Product Description

Produced by General Electric Multilin, the 12M9-008-B2 is a revision of the IO_C module designed for the MM300 Motor Manager system. The IO_C module offers two form-A contact output relays, six digital inputs, and control voltage input. The contact inputs are programmable for any of the input functions, i.e. process interlock or field stop functions. This is true except for contactor A and contactor B, which are fixed as the first and second contact inputs respectively. The user is able to program the two contact inputs to follow any of the digital signals developed by the MM300, such as status signals and alarms. 

Terminals 12 and 13 are built to connect to an AC auxiliary supply. The auxiliary voltage can be used for actual value indication, for undervoltage restart, and auxiliary undervoltage. In the event that three-phase voltages are not available, the AC auxiliary supply is also used to calculate power quantities and is used as a phase angle reference. In the event that the IO_C module detects an interruption to the auxiliary supply (while located in slot C), it is capable of raising an AC Low Aux Voltage Inhibit. It then forces the input state of contact inputs to the OFF setting, since the interruption prevents sensing actual states. 

Installation of the IO_C module is simple when following the guide located in any of the user manuals. Users should try to reference the most recent revision of the manual available; fortunately, Multilin’s EnerVista MM300 software program is capable of automatically updating system documents and can provide it readily to the buyer. 

Frequently Asked Questions about 12M9-008-B2

What is the 12M9-008-B2?

A module for the MM300 Motor Management series, the 12M9-008-B2 is a revision of the IO_C module produced by General Electric Multilin. The IO_C module offers six digital inputs, two form-A contact output relays, and control voltage input.

What are some of the important notes about the 12M9-008-B2?

It is important to connect the AUX VT to the Control Supply for correct operation of the readings of inputs UV and Restart feature. Additionally, all IO_C cards must have the auxiliary input VT wired for accurate input sensing. In the event that auxiliary voltage on any IO-C module is too low, the contact inputs states for the module experiencing the issue will be forced to OFF. More operational notes of this nature can be found in the AX Control user manual. 

Reviews For 12M9-008-B2

Internal Review
(5.0)

Users can run a dielectric test while the IO_C relay is installed in the MM300 unit, allowing users to assess the health of insulation materials within the MM300. The MM300 with the I/O Module type C installed is rated for 1.9 kV AC for one second, or 1.6 kV AC for one minute isolation between relay contacts and VT and CT inputs. - AX Control Tech

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More