469-P5-LO-A20

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.00 (1)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.00 (1)
  • Click a star to rate this product
Motor Management Relay by GE Multilin with LO 20-60VDC and 20-48VAC at 48-62Hz

AVAILABILITY:

IN STOCK
SHIPS IN 3-5 DAYS

Contact: 1-919-372-8413 (Intl.), 1-800-991-7026 (US), sales@axcontrol.com

Warranty: Learn More

Sell Surplus: Have a 469-P5-LO-A20 to sell? Sell Now

Exchange Credit: Learn more about our exchange credit program

469-P5-LO-A20

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.00 (1)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.00 (1)
  • Click a star to rate this product
Motor Management Relay by GE Multilin with LO 20-60VDC and 20-48VAC at 48-62Hz

AVAILABILITY:

IN STOCK
SHIPS IN 3-5 DAYS

Contact: 1-919-372-8413 (Intl.), 1-800-991-7026 (US), sales@axcontrol.com

Warranty: Learn More

Sell Surplus: Have a 469-P5-LO-A20 to sell? Sell Now

Exchange Credit: Learn more about our exchange credit program

Frequently Asked Questions about 469-P5-LO-A20

What should the phase CTs, ground CTs, and motor full load current be set for the GE 469-P5-LO-A20 Relay?
For the GE 469-P5-LO-A20 Relay the phase CTs have to be chosen for the full load current at 50 percent to 100 percent of a primary CT, but with the full load current is 347.5A a 350:5, or 400:5 CT can be picked  and  the 400:5 is standard for the size that is selected. The high resistive grounding systems are senstive to ground detection and are possible with the 50:0.025 CT. Setting the motor full load current to 348A is specified by the other data sheets of the phase current transformers and ground current transformers.
What are the over load pick up and over load curve settings for the GE Motor Management Relay's?
The over load pick up setting should be on the highest service factor of 1.25 x full load current, so that the motor service factor is at 1.15 and if the service factor is unknown, then it should be automatically set to 1.0. This motor has resistance temperature detectors (RTDs) that the relay with be using to protect the over load pick up. For the over load curve to not compromise the protection on the relay, the over load curve should be set at the standard over load curve and to have the most process up time, it will be just below the cool thermal limit. Over load curve 7 is the best fitting for this relay.

Repair Services For 469-P5-LO-A20

Type Lead Time Price Action
Repair Service 1-2 weeks Ask Get Quote

Our highly skilled technicians can repair your 469-P5-LO-A20. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More