What does the diagnostic readout 001001, 001010, 001011, 001100, 001101, 001110 mean?
The diagnostic readout 001001, 001010, 001011, 001100, 001101, 001110 has a fault number FL73, FL74, FL75, FL76, FL77, FL78, and fault names A1ROP, A2ROP, A3ROP, A4ROP, A5ROP, A6ROP (respectively) means the SCR AXR is not operating (L, T), where "X" = 1,2,3,4,5,or 6.
-The low current test maybe enabled - run a high current test.
-The Gate circuit is disconnected or open.
-The 5PL is disconnected or damaged.
-The SCR has failed - check and replace if necessary.
-Replace Power Connection card.
-Replace Control card.