Product Description
The 16 point, 4 Common DC Powered Output Module is part of Automation Direct's DL205 line. This specific piece was a collaboration between Koyo and PLC Direct. There are 4 points for each of the internally connected common. The workroom should stay at an ambient temperature of 0 and 55 degrees Celsius. The device's storage space should stay between -20 and 70 degrees Celsius. The dimensions of the module are 3.5 x 3.15 x 3.28 and weighs 140g. There is a logic side status indicator that alerts the user of problems.
The 16 point, 4 Common DC Powered Output Module's operating voltage range is between 6 and 27 VDC. The output voltage ranges between 5-30 VDC and the peak voltage is 50 VDC. The module also has a maximum leakage current of 15 μA @ 30 VDC. The maximum output current per point is 1 amp and 4 amps per common. The inrush current for the device is 2 amps for 100 milliseconds.
The base power required to run the module is 200 mA @ 5 VDC and it needs external power of 400mA from 20 to 28 VDC. There are 4 fuses that connect to the system with personal status indicators.
The searchable product number of the 16 point, 4 Common DC Powered Output Module is T1K-16TD1. The module is compatible with both the T1K-16B and T1K-16B-1 bases. The product numbers of the instruction booklets are the T1K-INST-M and T1H-DM-M manuals. Call us now to get pricing quotes and information about our warranties.