Product Description
easYgen 3000 model 8440-2055 is designed for the cabinet back mounting. There is no built-in HMI with this model. Instead, configuration and operations are managed via PC using ToolKit software.
Part 8440-2055 may be used for both single and multiple unit operations, including mains parallel operation for up to 32 units, for a variety of applications. Four operating modes are available with this genset controller: Automatic, Manual, Stop, and Test. Full control features and additional product specifications may be found in Woodward easYgen 3000 manual 37258P.
Numerous setpoints may be configured to meet the requirements of various applications. The 8440-2055 model offers protection against generator overload or unbalanced load, engine over speed or under speed conditions, engine speed/frequency mismatch, mains phase shift/rotation field issues, and much more.
Speed input is measured using magnetic / switching pickup (50/60 Hz measuring frequency). Part 8440-2055 has discrete I/Os and analog I/Os. Both types of inputs/outputs are configurable. Ten of the twelve alarm outputs are configurable.