Frequently Asked Questions about 760-P5-G5-S5-HI-A10-R
What does it mean when the breaker state bypass is enabled for the GE Feeder Management Relay for the part number 760-P5-G5-S5-HI-A10-R?
When the breaker state bypass "BRKR STATE BYPASS" for the GE Feeder Management Relay 760-P5-G5-S5-HI-A10-R is enabled, it means that the close coil supervision circuits ane the trip can monitor them continuouly and not affected by the breaker state.
What input can be connected for external contacts on the Ge Feeder Management Relay for the 760-P5-G5-S5-HI-A10-R?
For external contacts on the 760-P5-G5-S5-HI-A10-R, you should connect them to the relay's fourteen logic input. It does not matter if the contact is either wet or dry, but you can use a combination of both contacts.
What is the difference between a wet contact and a dry contact connection for 760-P5-G5-S5-HI-A10-R?
To have a dry contact, you have to connect one side to the terminal C12 and its the +32 V DC voltage rail. The dry contacts other side should be connected to the required logic input terminal. For a wet contact you must have one side connected to a (+)positive terminal on the external direct current power supply. Connect the other side of the contact to the logic input terminal that is required, also the (-)negative side of the outside source should be connected to terminal D12 of the relay's direct current (-)negative rail.