In Stock
565-5-5-M Image One
3 year warranty

565-5-5-M Image 1
565-5-5-M Image 2
565-5-5-M Image 3

565-5-5-M

    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.67 (3)
  • Click a star to rate this product
    Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures Varying star amount pictures
  • 4.67 (3)
  • Click a star to rate this product
The 565-5-5-M relay is a Digital Feeder Management Relay made for the 565/575 Series. This model operates on a phase and ground current of 5 AMPS. Real-time actual values can be shown on the display screen of this device.

AVAILABILITY:

IN STOCK
SHIPS TODAY

Sell Surplus: Have a 565-5-5-M to sell? Sell Now
Exchange Credit: Learn more about our exchange credit program
  • Part Number: 565-5-5-M
  • SKU: 56555MGM
  • Manufacturer: GE Multilin
  • Series: 565/575 Feeder Management Relay

565-5-5-M Technical Specifications

Manufacturer General Electric Multilin (GE)
Manufacturing Location Markham, Ontario, Canada
Model Number 565-5-5-M
Function of Terminal 62 Control Voltage GND
Mounting Application Panel Mount
Port Type RS232 Program Port
Slave Response Transmission Function Code - 1 Byte
Terminals for Voltage Transformers 35 to 38
Auxiliary 4 Contacts 30 N.O., 31 Common, and 32 N.C.
Choice Quantity for Testing Output Relay Contacts 5; Aux 1, 2, 3, and All
Function of 14H Operation Code Clear Events

Product Description

Marketed as a Digital Feeder Management Relay, the 565-5-5-M model is primarily used in applications in which protection and management of high and medium-voltage distribution systems is required. Each character in the part number is important as it indicates the different functions of the device such as the ground and phase current inputs shown by the two fives following the 565 (which simply indicates what series the machine is part of). The relay must be mounted as a panel mount. Users should ensure that the device is mounted in a location where the keypad and LCD on the front of the relay are still easily accessible. 

A multitude of messages can be shown on the display screen of the 565-5-5-M relay, some of which include the actual values monitored by the system. There are twenty-one typical messages that will pop up pertaining to the actual values which include phase (PH), degrees celsius (DEG C), overcurrent (O/C), access (A), and many more. The comprehensive list of the messages and their abbreviations can be found in the fourth chapter of the GE 1601-0017 E2.73 565-575 Feeder Management Relay Instruction Manual attached above. Users can edit system settings to specify which parameters appear passively when the LCD is not in active use.

Relay testing is available to ensure proper functionality of the device. Some of the testing types available on the 565-5-5-M relay are primary and secondary injection testing. The primary injection relay testing is done by injecting a current through both the ground and phase CTs which will provide a potential source. Operation of the entire system, including the CTs, can be checked when using a high current test set. 

Frequently Asked Questions about 565-5-5-M

What is the 565-5-5-M?

General Electric Multilin's 565-5-5-M protects, controls, and manages three phase feeder distribution systems, safeguarding both equipment and personnel alike. It can be configured to monitor phase current, ground current, and voltage in the network and subsequently run protective functions when necessary. 

What are the features of the inputs and outputs of the 565-5-5-M unit?

The relay inputs can be used for indication of external differential trips or breaker status. One of the assigned inputs is "Analog Select", which can be connected to four dry contacts of a PLC (programmable logic controller). It can forward requested actual values (such as individual phase currents) and the relay can send the requested value through the output terminal in either 0-1mA format or 4-20mA format. In terms of outputs, the relay offers six electromechanical output relays dubbed "Trip", "Close", and "Aux" 1-4. The flexible software programming allows the output relays to be assigned various functions.

Reviews For 565-5-5-M

Internal Review
(5.0)

The 565-5-5-M relay is used for the protection of three-phase readers. The relay will protect not only the user but the equipment from any type of potential injury and damage if fault conditions occur. - AX Control Technician

Repair Services For 565-5-5-M

Type Lead Time Price Action
Repair Service 1-2 weeks $1078

Our highly skilled technicians can repair your 565-5-5-M. All of our repairs come with a 3 Year AX Control Warranty. Please contact us for additional information about our repair process. To receive the repair pricing and lead time listed above please process your repair order via our website. The following repair options may be available upon request:

  • 48-72hr Rush Repair
  • Detailed Repair Reports
  • AX Control Certificate of Warranty

AX Control Warranty Info

All products we sell are backed by our unparalleled warranty. A warranty certificate will be provided with your order upon request.
All PLCs, HMIs, and Turbine Control Boards: 3 Years
All AC/DC and Servo Drives: 2 Years
All Motors: 1 Year
Learn More