GE Vernova MVAX 12, 21, 31, 91 Trip Circuit Supervision
The MVAX relays are designed to supervise trip circuits of the circuit breakers. The relays will initiate alarms and visual indications if the trip circuit fails or the mechanism does not operate. The trip circuit can be monitored when the breaker is both open and closed. The MVAX maintains the integrity of the protection scheme. There are four types of MVAX relays, which are the MVAX 12, MVAX 21, MVAX 31 and MVAX 91.
The MVAX 12 can be used for detecting a failure in the trip supply only, which is the same for the MVAX 21. The MVAX 12 is made up of only one unit. The MVAX 12 is normally energized and drops off if the trip voltage is lost or or falls below 40% of the nominal voltage. MVAX 21 is made up of two units and can only be used with the circuit breaker closed. The MVAX 21 normally has both units energized unless the trip circuit opens or if the supply fails.
The MVAX 31 and 91 can be used for open circuit coil trip or trip circuit wiring failure of the circuit breaker tripping mechanism. The MVAX 31 is made up of three connected units. When the circuit breaker is closed with healthy conditions, units RL2 and RL1 are energized. When the circuit breaker is open, unit RL3 is also energized. Unit RLR3 will detect abnormalities when the breaker is open, while unit RL2 will detect abnormalities when the breaker is closed. The MVAX 91 is made up of three MVAX 31 units. The MVAX relays are used to detect abnormalities within the trip circuits of circuit breakers.