A History of GE Speedtronic Turbine Control

GE has a long history of providing industrial control systems for gas and steam turbines.

Cross-section of a GE industrial gas turbine

A History of Turbine Science

Gas turbine theory is not new to the world; in fact, Leonardo Da Vinci designed a reaction-type turbine that, while nothing like turbines of today, harnessed the power of burning gases within an enclosed space. Da Vinci’s ‘chimney jack’ used hot air rising from a hearth to turn an axial rotor attached to a roasting spit located over the fire. In this way, food on the spit turned without need for an attendant.

 GE was one of the first modern companies to understand the power of turbine applications, which have been used in such high profile locations as Niagara Falls (1918) and the Grand Coulee Dam project (1942). Their gas turbine division, which is now over a century old, was instrumental in advancing gas turbine jet engine design as well as commercializing the use of industrial gas turbines for the first time.  These turbines have been used for power generation in nuclear power plants, in steam turbines and boiler systems, as well as in combined-cycle gas turbine plants. 

Download a high quality pdf of these characteristics.

Beginning in the 1960s and continuing through the early 2000s, GE also developed and sold sophisticated turbine control systems for their gas and steam turbines.   These control systems were sold under the SPEEDTRONIC trademark name, starting with the Mark I series and continuing through the release of the Mark VIe. While each system had significant improvements over the previous release, there are still a number of Mark I and Mark II control systems in active use around the world today.  The longevity of these systems can be attributed to GE’s adherence to specific gas and steam turbine control philosophies that emphasized “safety of operation, reliability, flexibility, maintainability, and ease of use, in that order,” according to company documents. The gas philosophy maintains: 

  • Single control failure alarms when running or during startup
  • Protection backs up control, thus independent 
  • Two independent means of the shutdown will be available 
  • Double failure may cause a shutdown, but will always result in a safe shutdown
  • Generator-drive turbines will tolerate full-load rejection without overspeeding  
  • Critical sensors are redundant 
  • Control is redundant
  • Any control systems problems will be alarmed
  • Standardize hardware and software to enhance reliability while maintaining flexibility

while the steam turbine control philosophy states

  • Clear separation between protection and control shall be provided
  • Controls shall comply with standard IEEE 122
  • All control functions shall have protection system backup
  • A double set of steam valves shall be provided for major admissions including one set for protection and one for controls
  • Protection (aka trips) shall be classified by criticality.
  • All important and vital functions use two out of three redundancy from sensor to actuator.
  • A single control failure will not cause a shutdown but instead will cause a diagnostic alarm that is repairable online.

Types of GE Control Systems

Mark I turbine control was originally released in the late 1960s.  MKI’s averaged fifty PCBs (printed circuit boards) per control panel and offered three input loops, including a start-up, temperature, and speed loop.  The Mark I worked on a “redundancy by association” philosophy. This meant while the system operated on one control, say temperature, it was backed up by the speed control.  This gave the system a process fail-safe, although not to the same level of later, more sophisticated systems like the Mark IV.  

The Mark II improved upon the Mark I by introducing solid-state integrated circuits and a new cabinet arrangement.   The circuitry allowed complex functions like combustion monitoring to be practical for the first time.   

Control in both the Mark I and Mark II was powered by three loops (startup/speed/temperature) where whichever parameter requiring the least amount of fuel took precedence.  The output of this minimum value gate was described as VCE (electronic control voltage.) This value determined how much fuel was used. Sequencing in the MKI used 28 VDC relays.  The MKII used digital logic software for sequencing.  

Interestingly, while GE designed a Mark III system, very few units were actually sold, and only for the electro-hydraulic market, none for gas turbine control.   This control system was designed with integrated circuits and was the first of the control systems to utilize microprocessors. It was also the first to offer triple modular control, but only for steam turbines. However, it was used only on small and medium-sized turbine systems, limiting its market. 

DS3800NADA1F1F Analog to Digital Converter Card for Mark IV Speedtronic

The Mark IV was the first GE turbine control system that offered triple modular redundant control for both gas and steam turbines.  Control calculations were made digitally, an improvement over previous analog systems.  Mark IV communications used RS-232 or RS-485 transmission between the MKIV passive client and devices.

What is TMR Control? 

Triple Modular Redundant control is a design with built-in redundancy.  The system has three microprocessor controllers (in the case of the Mark IV, named <R>, <S>, and <T>).  There is also a <C> communications microprocessor. The system is designed with two-out-of-three voting, where each controller independently votes on conditions like temperature, over speed, valve position, etc.  As long as two of the three agree, the system continues to run.  

The Mark IV introduced a more user-friendly CRT operator interface that would display the state of logic functions and values.   The display made it easier for operators to change values when needed, which could be done from the panel, vs. the previous method of finding the proper potentiometer on the correct board, and adjusting manually using a connected voltmeter.  

High-Frequency Power Supply Board for Mark V system

When the Mark V was introduced in 1991, it could be set up as either a TMR or a Simplex control system.  One of the most significant improvements over the Mark IV was the change to software-implemented fault tolerance (SIFT), which helped fuel command signals to the digital servo remain synced.   The MKV could be used for steam or gas turbines to drive compressors, pumps, or generators. Operator interface to the Mark V could be set up with an <I> Interface Data processor that consisted of a monitor, keyboard, and printer,  or the system could be accessed via HMIs (human-machine interface.) The operator interface is typically set up to handle any communication with remote or external devices that might be necessary. 

It is important to note that–in most cases–HMIs and/or the I/O are connected for data gathering and troubleshooting rather than for control purposes. 

GE Bridge Application Interface Board. From a Mark VI Control System.

The Mark VI was designed by General Electric with a central Control Module that received inputs through termination boards using passive signal conditioning.  This system could be designed in TMR or Simplex form and offered control, protection, and monitoring functions through the Control Module.  

Are OEM upgrades available?

The Mark VIe was marketed by General Electric as a “plug and play” upgrade migration for those looking to find an OEM solution for legacy systems like the Mark I, Mark II, and Mark IV.   GE designed the Mark VIe with a wide variety of options, including single, dual, and TMR controllers supported by single, dual, or shared I/O. These could be set up locally or in a remote location using the Mark VIe’s ethernet capabilities (also offered across single, dual or TMR networks.)   

While it is true the MKVIe offers extended capabilities to users, some of the Mark VIe components have now also been given legacy status by GE and are no longer supported by the OEM, which leaves them in the same situation as previous models. It’s likely the entire Mark VIe will become obsolete at some point. Additionally, parts remain available for previous systems for those who wish to keep their current configurations.   Partnering with a reliable distributor with knowledgeable techs who can perform maintenance and repair on your components can also extend the lifespan of your system.

The MKVIe can be used in a wide variety of industries, including nuclear facilities, thermal or wind applications, or in hydro-electric, oil and gas systems.    This is a Distributed Control System(DCS) with autonomous controllers distributed throughout.  

How to Decode Your GE Part Number

GE Speedtronic boards followed a standard protocol for naming throughout most of their production, with some minor changes. Each series of boards typically had an original run, then had upgrades released later. In each series, the upgraded series will have a similar part number to the original board. For example, IS200ACLEH1A and IS215ACLEH1A are the same Mark VI board with the exception of the updated firmware available on the IS215board. Both cards function as Application Control Layer Modules.

When you’re running legacy systems, it may be important to understand how part numbers migrate from one production run to another in order to more easily locate useful manuals for your parts. While you may not be able to locate a manual for the IS200ACLEH1A mentioned above, the IS215ACLEH1A manual is still widely available and has sections that relate to both cards. Part number conventions are typically printed in the Renewal/Warranty Replacement section of hardware manuals.